5-264
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
INPUTS/OUTPUTS
CHAPTER 5: SETTINGS
5
•
To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the
RESET
or
ENTER
pushbutton
•
All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the
RESET ANNUNCIATOR
setting. Then the Modbus execute function 05h with operation code 1000h command
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the
RESET ANNUNCIATOR
setting, the
RESET ANCTR OP
FlexLogic operand is activated by the two sources of
RESET
command, operand source and manual source. Each individual source of a
RESET ANNUNCIATOR
command also activates
its individual operand
RESET OP (OPRD)
or
RESET ANCTR OP (MNUL)
to identify the source of the command. Each of these two
operands generates an event in the event record when activated. The setting here selects the operand that activates the
RESET ANCTR OP (OPRD)
operand. The
RESET
pushbutton on the front panel or the reset command from the software
activates the
RESET ANCTR OP (MNUL)
operand.
5.9.6 Direct inputs and outputs
5.9.6.1 Direct inputs
SETTINGS
INPUTS/OUTPUTS
DIRECT INPUTS
DIRECT INPUT 1(32)
These settings specify how the direct input information is processed.
DIRECT INPUT 1 NAME
— This setting allows the user to assign a descriptive name to the direct input.
DIRECT INPUT 1 DEVICE ID
— Represents the source of direct input 1. The specified direct input is driven by the device
identified here.
DIRECT INPUT 1 BIT NUMBER
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as
DIRECT INPUT 1 BIT NUMBER
. This corresponds to the direct output number of the sending device.
DIRECT INPUT 1 DEFAULT STATE
— Represents the state of the direct input when the associated direct device is offline. The
following choices are available:
•
On — Defaults the input to Logic 1
•
Off — Defaults the input to Logic 0
•
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
•
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.9.6.2 Direct outputs
SETTINGS
INPUTS/OUTPUTS
DIRECT OUTPUTS
DIRECT OUTPUT 1(32)
DIRECT INPUT 1
DIRECT INPUT 1
NAME: Dir Ip 1
Range: up to 12 alphanumeric characters
DIRECT INPUT 1
DEVICE ID: 0
Range: 0 to 16
DIRECT INPUT 1
BIT NUMBER: 0
Range: 0 to 32
DIRECT INPUT 1
DEFAULT: Off
Range: On, Off, Latest/On, Latest/Off
DIRECT INPUT 1
EVENTS: Disabled
Range: Enabled, Disabled
DIRECT OUTPUT 1
DIRECT OUT 1 NAME:
Dir Out 1
Range: up to 12 alphanumeric characters
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...