2-30
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k
Ω
for –1 to 1 mA range
12 k
Ω
for 0 to 1 mA range
600
Ω
for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change:
100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001
2.5.8 Communication protocols
IEC 61850
IEC 61850:
Supports IEC 61850 Edition 2.0. See the UR Family Communications Guide and its conformance
statements.
RS232 (Enhanced and standard front panels)
Front port:
19.2 kbps, Modbus RTU
USB (Graphical front panel)
Front port:
USB 2.0 type B
RS485
1 rear port:
up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance:
1200 m
Isolation:
2 kV, isolated together at 36 Vpk
FIBER ETHERNET PORT
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
10 Mb, 10/100 Mb (auto-detect)
Connector:
RJ45
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Clock synchronization error:
<10 ms (typical)
PRECISION TIME PROTOCOL (PTP)
PTP IEEE
Std
1588
2008 (version 2)
Power Profile (PP) per IEEE
Standard
PC37.238TM2011
Slave-only ordinary clock
Peer delay measurement mechanism
Parameter
Fiber type
100 Mb multimode
Wavelength
1310 nm
Connector
LC
Transmit power
–20 dBm
Receiver sensitivity
–30 dBm
Power budget
10 dB
Maximum input power
–14 dBm
Typical distance
2 km
Full duplex
yes
Redundancy
yes
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...