AF-650 GP 3-phase
Recommended fuse size
Recommended max fuse
[kW]/[HP]
0.37/1/2
gG-20
gG-32
0.75/1
1.5/2
2.2/3
3.7/5
5.5/7.5
7.5/10
11/15
gG-50
gG-80
15/20
18.5/25
gG-80
gG-100
22/30
30/40
gG-125
gG-160
37/50
45/60
55/75
aR-250
aR-250
75/100
90/125
gG-300
gG-300
110/150
gG-350
gG-350
132/200
gG-400
gG-400
160/250
gG-500
gG-500
200/300
gG-630
gG-630
250/350
aR-700
aR-700
315/450
aR-900
aR-900
355/500
400/550
450/600
aR-1600
aR-1600
500/650
560/750
aR-2000
aR-2000
630/900
710/1,000
aR-2500
aR-2500
800/1200
Table 13.8 380–480 V, IP55/Nema 12 and IP66/Nema 4X
Specifications
AF-650 GP
TM
Design and Installation Guide
13-22
DET-767A
13
3
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...