6.4.3 Reference Limits
F-50 Reference Range
,
F-52 Minimum Reference
and
F-53 Maximum Reference
together define the allowed range
of the sum of all references. The sum of all references is
clamped when necessary. The relation between the
resulting reference (after clamping) and the sum of all
references is shown below.
Figure 6.12
Figure 6.13
The value of
F-52 Minimum Reference
cannot be set to less
than 0, unless
H-40 Configuration Mode
is set to
[3] Process
.
In that case, the following relations between the resulting
reference (after clamping) and the sum of all references is
as shown in
Figure 6.14 Sum of all References
6.4.4 Scaling of Preset References and Bus
References
Preset references are scaled according to the following
rules:
•
When
F-50 Reference Range
: [0] Min - Max 0%
reference equals 0 [unit] where unit can be any
unit, e.g., rpm, m/s, bar, etc. 100% reference
equals the Max (abs (
F-53 Maximum Reference
),
abs (
F-52 Minimum Reference
)).
•
When
F-50 Reference Range
: [1] -Max - +Max 0%
reference equals 0 [unit] -100% reference equals -
Max Reference 100% reference equals Max
Reference.
Bus references are scaled according to the following rules:
•
When
F-50 Reference Range
: [0] Min - Max. To
obtain max resolution on the bus reference, the
scaling on the bus is: 0% reference equals Min
Reference and 100% reference equals Max
reference.
•
When
F-50 Reference Range
: [1] -Max - +Max
-100% reference equals -Max Reference 100%
reference equals Max Reference.
Application Setup Examples
AF-650 GP
TM
Design and Installation Guide
6-12
DET-767A
6
6
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...