Mount the unit to a solid flat surface or to the
optional backplate to provide cooling airflow (see
•
Improper mounting can result in overheating and
reduced performance.
•
Use the slotted mounting holes on the unit for
wall mounting, when provided.
Figure 2.7 Proper Mounting with Backplate
Item A is a backplate properly installed for required airflow
to cool the unit.
Figure 2.8 Proper Mounting with Railings
NOTE!
Backplate is needed when mounted on railings.
2.3.5 IP21 Drip Shield Installation (Unit
Sizes 41 and 42)
To comply with the IP21 rating, a separate drip shield is
to be installed as explained below:
•
Remove the two front screws.
•
Insert the drip shield and replace the screws.
•
Torque the screws to 5.6 Nm (50 in-lbs).
Figure 2.9 Install the drip shield.
2.4 Field Installation of Options
2.4.1 Installation of Top-only Duct Cooling
Kit
This description is for the installation of the top section
only of the backchannel cooling kits available for unit sizes
43, 44 and 52. In addition to the enclosure, an 8 in [200
mm] vented pedestal is required.
The minimum enclosure depth is 19.7 in [500 mm] (23.6 in
[600 mm] for unit size 52) and the minimum enclosure
width is 23.6 in [600 mm] (31.5 in [800 mm] for unit size
52). The maximum depth and width are as required for the
installation. When using multiple adjustable frequency
drives in one enclosure mount each drive on its own back
panel and support along the mid-section of the panel. The
back-channel cooling kits are very similar in construction
for all frames. The kits do not support “in frame” mounting
of the adjustable frequency drives. The 52 kit is mounted
“in frame” for additional support of the adjustable
frequency drive.
Using these kits as described removes 85% of the losses
via the backchannel using the drive’s main heatsink fan.
The remaining 15% must be removed via the door of the
enclosure.
Installation
AF-650 GP
TM
Design and Installation Guide
2-4
DET-767A
2
2
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...