11 Basic Troubleshooting
11.1 Start Up and Operation
Symptom
Possible cause
Test
Solution
Display dark/No function
Missing input power.
See
Check the input power source.
Missing or open fuses or circuit
breaker tripped.
See open fuses and tripped circuit
breaker in this table for possible
causes.
Follow the recommendations
provided.
No power to the keypad.
Check the keypad cable for proper
connection or damage.
Replace the faulty keypad or
connection cable.
Shortcut on control voltage
(terminal 12 or 50) or at control
terminals.
Check the 24 V control voltage
supply for terminals 12/13 to 20-39
or 10 V supply for terminals 50 to
55.
Wire the terminals properly.
.
Wrong contrast setting.
Press [Status] + [
▲
]/[
▼
] to adjust
the contrast.
Display (keypad) is defective.
Test using a different keypad.
Replace the faulty keypad or
connection cable.
Internal voltage supply fault or
SMPS is defective.
Contact
supplier.
Intermittent display
Overloaded power supply (SMPS)
due to improper control wiring or
a fault within the adjustable
frequency drive.
To rule out a problem in the
control wiring, disconnect all
control wiring by removing the
terminal blocks.
If the display stays lit, then the
problem is in the control wiring.
Check the wiring for shorts or
incorrect connections. If the display
continues to cut out, follow the
procedure for display dark.
Basic Troubleshooting
AF-650 GP
TM
Design and Installation Guide
DET-767A
11-1
11
11
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...