9.2.5.6 Parameter Values
Standard data types
Standard data types are int16, int32, uint8, uint16 and
uint32. They are stored as 4x registers (40001–4FFFF). The
parameters are read using function 03HEX "Read Holding
Registers." Parameters are written using the function 6HEX
"Preset Single Register" for 1 register (16 bits), and the
function 10 HEX "Preset Multiple Registers" for 2 registers
(32 bits). Readable sizes range from 1 register (16 bits) up
to 10 registers (20 characters).
Non standard data types
Non-standard data types are text strings and are stored as
4x registers (40001–4FFFF). The parameters are read using
function 03HEX "Read Holding Registers" and written using
function 10HEX "Preset Multiple Registers." Readable sizes
range from 1 register (2 characters) up to 10 registers (20
characters).
9.3 Drive Control Profile
9.3.1 Control Word According to Drive
Profile (
O-10 Control Word Profile
=
Drive profile)
Figure 9.2
Bit
Bit value = 0
Bit value = 1
00
Reference value
external selection lsb
01
Reference value
external selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output
frequency
use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 02 active
13
Parameter setup
selection lsb
14
Parameter setup
selection msb
15
No function
Reverse
Table 9.14
Explanation of the Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in
C-05 Multi-
step Frequency 1 - 8
according to the following table:
Programmed ref.
value
Parameter
Bit 01
Bit 00
1
C-05 Multi-step
Frequency 1 - 8
[0]
0
0
2
C-05 Multi-step
Frequency 1 - 8
[1]
0
1
3
C-05 Multi-step
Frequency 1 - 8
[2]
1
0
4
C-05 Multi-step
Frequency 1 - 8
[3]
1
1
Table 9.15
Bit 02, DC brake:
Bit 02 = ’0’ leads to DC braking and stop. Set braking
current and duration in
B-01 DC Brake Current
and
B-02 DC
Braking Time
. Bit 02 = ’1’ leads to ramping.
RS-485 Installation and Set...
AF-650 GP
TM
Design and Installation Guide
DET-767A
9-7
9
9
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...