13.3.5 NEC and UL Compliance
Fuses or Circuit Breakers must comply with NEC 2009. We recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 600 V
depending on the adjustable frequency drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating
(SCCR) is 100,000 Arms.
Recommended max. fuse
AF-650 GP
Power
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[kW]/[HP]
Type RK1
1)
Type J
Type T
Type CC
Type CC
Type CC
0.25–0.37/
1/3–1/2
KTN-R-05
JKS-05
JJN-05
FNQ-R-5
KTK-R-5
LP-CC-5
0.75/1
KTN-R-10
JKS-10
JJN-10
FNQ-R-10
KTK-R-10
LP-CC-10
1.5/2
KTN-R-15
JKS-15
JJN-15
FNQ-R-15
KTK-R-15
LP-CC-15
2.2/3
KTN-R-20
JKS-20
JJN-20
FNQ-R-20
KTK-R-20
LP-CC-20
3.7/5
KTN-R-30
JKS-30
JJN-30
FNQ-R-30
KTK-R-30
LP-CC-30
5.5/7.5
KTN-R-50
KS-50
JJN-50
-
-
-
7.5/10
KTN-R-60
JKS-60
JJN-60
-
-
-
11/15
KTN-R-80
JKS-80
JJN-80
-
-
-
15/18.5/
20-25
KTN-R-125
JKS-125
JJN-125
-
-
-
22/30
KTN-R-150
JKS-150
JJN-150
-
-
-
30/40
KTN-R-200
JKS-200
JJN-200
-
-
-
37/50
KTN-R-250
JKS-250
JJN-250
-
-
-
Table 13.12 200–240 V
Recommended max. fuse
AF-650 GP
Power
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW]/[HP]
Type RK1
Type RK1
Type CC
Type RK1
3)
0.25–0.37/
1/3–1/2
5017906-005
KLN-R-05
ATM-R-05
A2K-05-R
0.75/1
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
1.5/2
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
2.2/3
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
3.7/5
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
5.5/7.5
5014006-050
KLN-R-50
-
A2K-50-R
7.5/10
5014006-063
KLN-R-60
-
A2K-60-R
11/15
5014006-080
KLN-R-80
-
A2K-80-R
15/18.5/
20-25
2028220-125
KLN-R-125
-
A2K-125-R
22/30
2028220-150
KLN-R-150
-
A2K-150-R
30/40
2028220-200
KLN-R-200
-
A2K-200-R
37/50
2028220-250
KLN-R-250
-
A2K-250-R
Table 13.13 200–240 V
Specifications
AF-650 GP
TM
Design and Installation Guide
DET-767A
13-25
13
13
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...