Function
Parameter
Setting
Restore the adjustable frequency drive
H-03
[2] Restore - make a power cycling - press reset
1) Set motor parameters:
Set the motor parameters according to nameplate
data
P-02 to P-07
F-04 & F-05
As stated on motor nameplate
Perform a full auto tune
P-04
[1] Enable complete auto tune
2) Check that motor is running in the right direction.
When motor is connected to an adjustable frequency drive with straight forward phase order as U - U; V- V; W - W motor shaft usually
turns clockwise seen into shaft end.
Press [“Hand”]. Check shaft direction by applying a
manual reference.
If motor turns opposite of required direction:
1. Change motor direction in
H-08 Reverse Lock
2. Turn off line power - wait for DC link to
discharge - switch two of the motor phases
H-08
Select correct motor shaft direction.
Set configuration mode.
H-40
[3] Process
Set Local Mode Configuration
H-45
[0] Speed Open-loop
3) Set reference configuration, i.e. the range for reference handling. Set scaling of analog input in parameter AN-##
Set reference/feedback units
Set min. reference (50° F [10
°
C])
Set max. reference (176° F [80
°
C])
If set value is determined from a preset value
(array parameter), set other reference sources to
No Function.
F-51
F-52
F-53
C-05
140° F [60
°
C] Unit shown on display
23ºF [-5
°
C]
95° F [35
°
C]
[0] 35%
Ref
=
Par
.
C
−
05(0)
100
× ((
Par
.
F
−
53)
−
(
par
.
F
−
52))
= 24, 5°
C
F-64 Preset Relative Reference
to
F-68 Relative Scaling Reference
Resource
[0] = No Function
4) Adjust limits for the adjustable frequency drive:
Set ramp times to an appropriate value as 20 s
F-07
F-08
20 s
20 s
Set min. speed limits
Set motor speed max. limit
Set max. output frequency
F-18
F-17
F-03
300 RPM
1,500 RPM
60 Hz
Set S201 or S202 to desired analog input function (Voltage (V) or milli-Amps (I))
NOTE! Switches are sensitive - Make a power cycling keeping default setting of V
5) Scale analog inputs used for reference and feedback
Set terminal 53 low voltage
Set terminal 53 high voltage
Set terminal 54 low feedback value
Set terminal 54 high feedback value
Set feedback source
AN-10
AN-11
AN-24
AN-25
PI-20
0 V
10 V
23° F [-5
°
C]
95° F [35
°
C]
[2] Analog input 54
6) Basic PID settings
Process PID Normal/Inverse
PI-30
[0] Normal
Process PID Anti Wind-up
PI-31
[1] On
Process PID start speed
PI-32
300 rpm
Save parameters to keypad
K-50
[1] All to keypad
Table 6.21 Example of Process PID Control setup
Application Setup Examples
AF-650 GP
TM
Design and Installation Guide
DET-767A
6-21
6
6
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...