![background image](http://html.mh-extra.com/html/ge/af-650-gp-series/af-650-gp-series_design-and-installation-manual_121818093.webp)
7.1.2 Emission Requirements
According to the EMC product standard for adjustable
speed adjustable frequency drives EN/IEC61800-3:2004, the
EMC requirements depend on the intended use of the
adjustable frequency drive. Four categories are defined in
the EMC product standard. The definitions of the four
categories together with the requirements for line power
supply voltage-conducted emissions are given in the table
below:
Category
Definition
Conducted emission requirement
according to the limits given in
EN55011
C1
adjustable frequency drives installed in the first environment (home and office)
with a supply voltage less than 1000 V.
Class B
C2
adjustable frequency drives installed in the first environment (home and office)
with a supply voltage of less than 1000 V, which are neither plug-in nor movable
and are intended to be installed and commissioned by a professional.
Class A Group 1
C3
adjustable frequency drives installed in the second environment (industrial) with a
supply voltage lower than 1000 V.
Class A Group 2
C4
Adjustable frequency drives installed in the second environment with a supply
voltage equal to or above 1000 V or rated current equal to or above 400 A or
intended for use in complex systems.
No limit line.
An EMC plan should be made.
Table 7.1
When the generic emission standards are used the
adjustable frequency drives are required to comply with
the following limits:
Environment
Generic standard
Conducted emission requirement
according to the limits given in EN55011
First environment
(home and office)
EN/IEC61000-6-3 Emission standard for residential, commercial and
light industrial environments.
Class B
Second environment
(industrial environment)
EN/IEC61000-6-4 Emission standard for industrial environments.
Class A Group 1
Table 7.2
Installation Consideration
AF-650 GP
TM
Design and Installation Guide
7-2
DET-767A
7
7
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...