13.2 General Technical Data
Line power supply
Supply voltage
200–240 V
±
Supply voltage
380–480 V
±
10%
Supply voltage
525–600 V
±
10%
Supply voltage
525–690 V
±
10%
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage.
Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency drive's lowest
rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. temporary imbalance between line phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW/10 HP
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW/15–100 HP
maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
90 kW/125 HP
maximum 1 time/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100kAIC RMS symmetrical Amperes, 240/480/600/
690 V maximum.
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency (0.34–100 hp)/(125hp) [(0.25–75 kW) / (75 kW)]
0–1,000 Hz
Output frequency (125–1,350 hp)/(150 hp) [(90–1,000 kW)/(90 kW)]
0–800
1)
Hz
Output frequency in flux mode
0–300 Hz
Switching on output
Unlimited
Ramp times
0.01–3600 s.
1)
Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque
maximum 180% up to 0.5 s
1)
Overload torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque (Variable torque)
maximum 110% for 60 s
1)
Overload torque (Variable torque)
maximum 110% for 60 s
Torque rise time in advanced vector control (independent of fsw)
10 ms
Torque rise time in in flux vector control (for 5 kHz fsw)
1 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4–5 x
torque rise time.
Digital inputs
Programmable digital inputs
4 (6)
1)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic'0' PNP
< 5 V DC
Voltage level, logic'1' PNP
> 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Specifications
AF-650 GP
TM
Design and Installation Guide
13-14
DET-767A
13
3
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...