Terminal description
Terminal
Parameter
Default
setting
Description
42
AN-50
[0] No
operation
Programmable analog
output. The analog
signal is 0–20 mA or
4-20 mA at a
maximum of 500
Ω
50
-
+10 V DC
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
53
AN-1#
Reference
Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
54
AN-2#
Feedback
55
-
Common for analog
input
Table 2.3
Terminal description
Terminal
Parameter
Default
setting
Description
Serial communication
61
-
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing
EMC problems.
68 (+)
O-3#
RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-)
O-3#
Relays
01, 02, 03
E-24
[0] No
operation
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
04, 05, 06
E-24
[0] No
operation
Table 2.4 Terminal Description
2.5.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in
1.
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in
2.
Insert the bared control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See
12 Terminal and Applicable Wire
for control terminal
wiring sizes.
Figure 2.20 Connecting Control Wiring
2.5.5.4 Using Shielded Control Cables
Correct shielding
The preferred method in most cases is to secure control
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the adjustable frequency
drive and the PLC is different, electrical noise may occur
that will disturb the entire system. Solve this problem by
fitting an equalizing cable next to the control cable.
Minimum cable cross-section: 0.025 in
2
(16 mm
2
).
Figure 2.21
1
Min. 0.025 in
2
[16 mm
2
]
2
Equalizing cable
Table 2.5
Installation
AF-650 GP
TM
Design and Installation Guide
2-12
DET-767A
2
2
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...