For the D, E, and F Frame sizes, this alarm is based on the
temperature measured by the heatsink sensor mounted
inside the IGBT modules. For the F Frame sizes, this alarm
can also be caused by the thermal sensor in the rectifier
module.
Troubleshooting
Check fan resistance.
Check soft charge fuses.
IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The network on the communication option card is not
working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the adjustable frequency drive is lost and
SP-10 Line failure
is NOT set to
[0] No Function
. Check the fuses to the
adjustable frequency drive and line power supply to the
unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
the table below is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your GE supplier or service
department. Note the code number for further trouble-
shooting directions.
No.
Text
0
Serial port cannot be restored. Contact your GE
supplier or GE Service Department.
256-258
Power EEPROM data is defective or too old
512
Control board EEPROM data is defective or too old.
513
Communication time out reading EEPROM data
514
Communication time out reading EEPROM data
515
Application oriented control cannot recognize the
EEPROM data.
516
Cannot write to the EEPROM because a write
command is on progress.
517
Write command is under timeout
518
Failure in the EEPROM
519
Missing or invalid barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-1279
A CAN message that has to be sent couldn't be
sent.
1281
Digital signal processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read digital signal processor software
version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1317
Option SW in slot C0 is not supported (not
allowed)
1318
Option SW in slot C1 is not supported (not
allowed)
1379
Option A did not respond when calculating
platform version
1380
Option B did not respond when calculating
platform version
1381
Option C0 did not respond when calculating
platform version.
1382
Option C1 did not respond when calculating
platform version.
1536
An exception in the application oriented control is
registered. Debug information written in keypad
1792
DSP watchdog is active. Debugging of power part
data, motor oriented control data not transferred
correctly.
2049
Power data restarted
2064-2072
H081x: option in slot x has restarted
2080-2088
H082x: option in slot x has issued a power-up wait
2096-2104
H983x: option in slot x has issued a legal power-
up wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
Warnings and Alarms
AF-650 GP
TM
Design and Installation Guide
DET-767A
10-5
10
10
Summary of Contents for AF-650 GP Series
Page 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Page 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Page 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Page 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Page 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Page 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Page 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Page 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Page 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Page 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Page 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Page 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...