G1000 NXi System Maintenance Manual
Page 152
King Air 300 Series
Revision 1
190-00716-N1
Channel
LRU
Indicator
Status
IN 6
GRS 77 or
GRS 7800
or GSU 75
#2
Green
GIA2/GRS or GSU 2 data path is functioning correctly.
Red
GIA2/GRS or GSU 2 data path is not functioning correctly.
•
Load GIA2 configuration files.
•
Swap GIA2 and GIA1, reconfigure both GIA’s to their
new locations to confirm if the problem is in the original
GIA2.
o
Replace original GIA2 if box turns green after
swapping units.
•
Swap GRS2 and GRS1 (no reconfiguration required)
to confirm if the problem is in the original GRS2.
o
Replace original GRS2 if box turns green after
swapping units.
•
Check the GIA2/GRS or GSU 2 interconnect wiring for
faults.
Amber
GIA2/GRS or GSU 2 data path functionality is unknown.
Reload GIA2 configuration files.