Revision 5
98
August 2021
Figure 65: Enron Modbus Format
The Enron Modbus format contains 4 nodes on the Modbus tree:
Coils
,
Short Integers,
Long Integers,
and
Floating Point
.
Coils
are Boolean (i.e. ON or OFF) data points
which have a value of either 0 or 1. Thus, points placed into the
Coils
should be points
that have only an ON or an OFF state, such as
Relay Status
points,
Fault Status
points,
or
Warning Status
points.
Control Command
points can also be placed into the
Coils
node for remote initiation of different commands.
Short Integers
are 16-bit whole
numbers with either a positive or a negative sign.
Long Integers
are 32-bit whole
numbers with either a positive or a negative sign.
Floating Point
values are also 32-bit
numbers, but unlike the integers they do not have a sign, but they do have decimal points.
Because the
Floating Point
node can display data that includes decimal points, it is the
most suitable node to use for the output of concentration data and other calculated
results.
5.3.2.2
Modicon 16 Format
If
Modicon 16
is chosen as the Modbus format , the Modbus list will contain 4 nodes as
shown in Figure 66.
Figure 66: Modicon 16 Format
The Modicon 16 Modbus format contains 4 nodes on the Modbus tree:
Output “Coils”
Status, Input Status, Input Register,
and
Output “Holding” Register
. The
Input
Status
and
Output “Coils” Status
nodes contain Boolean data points. Data points in
the Input Status node can be written to, so if any
Control Command
points are required,
they should be placed into the
Input Status
node. Data points in the
Output “Coils”
Status
node are read-only, so points placed into this node should include any data points
from the
Relay Status
,
Fault Status
, or
Warning Status
nodes, as data points in these
nodes are all read-only.
Output “Holding” Registers
are data points that are read-only
outputs of analyzer data, such as concentration values and calculated values like Air
Demand. The
Input Register
node is used for non-Boolean (i.e. numerical) data points
that can be written to.
The Modicon 16 format only outputs numerical data as 16-bit numbers. Thus,
the ouptut of decimal point data in this format is not possible – all numerical
data output in Modicon 16 is whole number only.
Summary of Contents for 943-TGS-CE
Page 137: ...Revision 5 137 August 2021 Figure 84 Oven Cabinet Details...
Page 138: ...Revision 5 138 August 2021 Figure 85 Control Cabinet Door Closed...
Page 139: ...Revision 5 139 August 2021 Figure 86 Control Cabinet Door Removed...
Page 140: ...Revision 5 140 August 2021 Figure 87 Power Steam Air Signals Connection Details...
Page 141: ...Revision 5 141 August 2021 Figure 88 AC Wiring Schematic...
Page 142: ...Revision 5 142 August 2021 Figure 89 DC Signals and Wiring Diagram...
Page 143: ...Revision 5 143 August 2021 Figure 90 Flow Diagram...
Page 144: ...Revision 5 144 August 2021 Figure 91 Control and Oven Cabinets Interconnect Wiring...