Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
67
Mixing Valve Control
Line no.
Programming line
938
Mixing valve cooling offset
941
Actuator running time
945
Mixing valve in heating mode
Mixing valve cooling offset
The cooling demand issued by cooling circuit 1 to
production is reduced by the adjusted value.
If there is a second zone, this reduction should
enable the second zone to be cooled. To achieve this
result, the sub-cooling must be determined in
accordance with the type of emitter and the
parameter 963 "With prim control/prim pump" must
be set to "yes" to switch on the pump for the second
zone.
Example:
Configuration
How the configuration affects control
Zone 1:
Heating/cooling
floor
Zone 2:
Fan coils
938 = 10°C,
with 924 = 18°C
963 = yes
with a 35°C outdoor temperature the flow
setpoint will be 18°C – 10°C i.e. 8°C
while in the first zone (HCF) it will be 18°C
through action of the mixing valve
Zone 1:
Heating/cooling
floor
Zone 2:
HCF
938 = 0°C,
with 924 = 18°C
963 = yes
with a 35°C outdoor temperature the flow
setpoint will be 18°C in both zones
WARNING:
If these settings are not chosen properly the heat
pump may stop automatically due to the flow
temperature being too low. A safety mechanism is
triggered at 6°C to protect the exchanger from
freezing.
Actuator running time
For the 3-position servomotor used, it is possible to
adjust the travel time. With a 2-position servomotor,
the adjusted travel time is inoperative.
Mixing valve in heating mode
Determines the position of mixing valve 1 (Y1 / Y2)
during heating operation is activated.
This parameter is inoperative in installations where
heating and cooling circuits are hydraulically
separate.
Control: the valve controls in heating and cooling
mode.
Open: the valve controls in cooling mode, and is open
in heating mode.
With prim controller/system pump
Line no.
Programming line
963
With prim contr/system pump
(no / yes)
This setting specifies whether the cooling circuit is
supplied from the primary controller or from the
primary pump (depending on the installation). It can
also be used to provide cooling to the second zone.
Warning:
In the case of a radiator or any other emitter which
does not support the cooling mode in zone 2, this
setting must remain on "No".