Split system (Single phase and 3-phase type)
96
Maintenance
Document
1544-1
6.1.5 FAN MOTOR removal
6.1.6 VALVE COVER removal
Remove the 4 mounting screws.
Remove the FAN GUARD by
sliding upward.
Remove the Hex Socket Screw. And
remove the PROPELLER FAN.
Note at the installation.
Insert propeller Fan and Moter shalf
reference D cutting position.
And the tightening torque at the
installation.
Tightening torque is from 10 to 15 N.M.
Cut the binder. (2 places)
Loose the clamp. (2 places) and
remove the lead wires.
Remove the 4 mounting screws.
Remove the FAN MOTOR.
Hook (4 places)
screw
Remove the mounting screws
Remove the VALVE COVER.
Single Phase type