Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
111
Thermistor (Discharge)
Thermistor (comp. Temp.)
Cut the binder, and remove
the heat insulation.
Remove the Thermistor (Discharge).
Remove the Thermistor (comp. temp.)
and the Thermistor (Discharge).
Remove the COMP BOLTS.
(3 places)
Cut the Discharge pipe in this range
Range
Range
Range
Cut the Suction pipe in this range.
Remove the COMPRESSOR.
Cut the Injection port in this range
Keep their shape better.
There is a possibility of catching fire to oil when removing by the welding without cutting it.
3-Phase type