Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
15
Clear 9: Outdoor temperature thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 4 flashes
Outdoor Unit LED: 7 flashes
Probable causes:
Misconnection.
Sensor
failure.
Main PCB failure.
Check:
1. Check the sensor connection :
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature
(°C) -20 -10 -5 0 5 10 15 20 30 40 50 60 70
Resistance (k
Ω
)
115 62,3 46,6 35,2 26,9 20,7 16,1 12,6 7,97 5,18 3,45 2,36 1,65
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
OK
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)
Summary of Contents for Waterstage WO G112LCT Series
Page 2: ......