Clear 33: Detection of compressor position error (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 5 flashes
Outdoor Unit LED: 14 flashes
Probable causes:
Misconnection.
Main PCB failure.
Check:
1.
Check connections condition in control unit
:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
OK
2. Replace the electronic board :
-
If steps 1 does not solve the problem, replace Main PCB.