Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
19
Clear 14: Expansion valve thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 8 flashes
Outdoor Unit LED: 6 flashes
Probable causes:
Misconnection.
Sensor
failure.
Main PCB failure.
Check:
1. Check the sensor connection:
-
See if the connector has been removed
-
See if the connection is correct
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature
(°C) 0 5 10 15 20 30 40 50
Resistance (k
Ω
) 168 130 101 79 63 40 26,3 17,8
Temperature (°C) 60
70
80
90 100 120
Resistance (k
Ω
) 12,3 8,7 6,3 4,6 3,4 2
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
OK
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)