2 Faults
2.1 Fault
List
2.1.1 Hydraulic Unit Fault
Faults which occur on the Hydraulic Unit are shown
by the symbol . Press the info key for details on the
cause of the fault. The following information is
displayed:
Description of the error
Location of the error (sensor or contact)
Reset. Depending on its type, the fault can be
manually or automatically deleted:
Manual delete: the text displayed when pressing
the info key shows "reset ?". Press OK once, the
yes flashes; press again to confirm deletion of the
fault.
Faults whose deletion is automatic are
automatically reset.
Heat pump op: shows whether or not the heat pump
operates despite the fault.
Reset
No.: Designation of error
Location
(connection)
Manual
Auto
HP op
10: Outdoor sensor
X86
No
No
Yes
33: Flow sensor HP
X70
No
No
Yes
44: Return sensor HP
X70
No
No
Yes
50: DHW sensor 1
X84
No
No
Yes
60: Room sensor 1
No
No
Yes
65: Room sensor 2
No
No
Yes
105: Maintenance message
No
No
Yes
121: Flow temp HC1 (too low)
No
No
Yes
122: Flow temp HC2 (too low)
No
No
Yes
127: Legionella temp
No
No
Yes
369: External fault (safety component)
No
370: Thermodynamic source*
No
No
No
No connection
the polarity of the
room sensor is not
respected.
-
-
No
* A fault in the outdoor unit is indicated by LED located on the Hydraulic Unit interface board.
LED display
LED 2 (green)
LED 1(red)
Fault description
1 Flash
1 Flash
Communication error between Hydraulic Unit and Outdoor unit.
4 Flashes
1 Flash
Heat pump capacity signal error (Open or short).
4 Flashes
2 Flashes
Hydraulic Unit heat-exchange thermistor Error.
6 Flashes
3 Flashes
Inverter error.
6 Flashes
4 Flashes
Active filter error.
7 Flashes
1 Flash
Discharge thermistor error.
7 Flashes
2 Flashes
Compressor thermistor error.
7 Flashes
3 Flashes
Heat-exchange thermistor (outlet) error.
Heat-exchange thermistor (intermediate) error.
7 Flashes
4 Flashes
Outdoor thermistor error.
7 Flashes
7 Flashes
Heat sink thermistor error.
7 Flashes
8 Flashes
Expansion valve thermistor error.
8 Flashes
4 Flashes
Current sensor error.
8 Flashes
6 Flashes
Pressure sensor error.
9 Flashes
4 Flashes
Current trip.
9 Flashes
5 Flashes
Detection of compressor position error.
Compressor start up error.
9 Flashes
7 Flashes
Outdoor unit fan motor error.
10 Flashes
1 Flash
Discharge temperature protection.
10 Flashes
3 Flashes
Compressor temperature protection.
10 Flashes
5 Flashes
Low pressure abnormal.
Continuous flashing (1 sec ON / 1 sec OFF)
Pump down operation.