Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
81
Simulation
Line no.
Programming line
7150
Simulation outside temp
Simulation outside temp (7150):
To make the starting-up and troubleshooting
processes easier, it is possible to simulate an outdoor
temperature in the range of -50...+50°C. During
simulation, the current, composite and attenuated
outdoor temperatures are ignored and substituted
with the adjusted simulation temperature.
Computation of the three outdoor temperatures
based on the actual outdoor temperature continues to
be performed during the simulation, and these
temperatures are available again when the simulation
is over.
This function can be deactivated by selecting -.- on
this line or automatically, after a 5 hour waiting
period.