Split system (Single phase and 3-phase type)
60
Maintenance
Document
1544-1
Reduced Setpoint Increase
Line no.
HC1
HC2
Programming line
800
1100
Reduced setpoint increase start
801
1101
Reduced setpoint increase end
This function is used mainly in heating installations
that do not have high supplies of power (e.g. low
energy homes). In that case, when outdoor
temperatures are low, adjusting the temperature
would be too long.
Increasing the reduced setpoint prevents excessive
cooling of the rooms in order to shorten the
temperature adjustment period when changing over
to the comfort setpoint.
Mixing Valve Control
Line no.
HC1
HC2
Programming line
830
1130
Mixer valve boost
834
1134
Actuator running time
Mixer valve boost
The controller adds the increase set here to the
current flow setpoint and uses the result as the
temperature setpoint for the heat generator.
Actuator running time
For 3-position control the valve Actuator running time
can be adjusted. With a 2-position servomotor, the
adjusted travel time is inoperative.
Controlled floor drying function
Line no.
HC1
HC2
Programming line
850 1150
Floor
curing
function
851
1151
Floor curing setpoint manually
856
1156
Floor curing day current
857
1157
Floor curing day completed
This function is used in the controlled drying of floors.
It adjusts the flow temperature to a temperature
profile. Drying is performed by floor heating via the
heating circuit with a mixing valve or with a pump.
Floor curing function
Off:
The function is deactivated.
Heating operational (Fh):
The first part of the temperature profile is
automatically completed.
Heating "ready for occupancy" (Bh)
The second part of the temperature profile is handled
automatically..
Heating "ready for occupancy" / Heating
operational
The full temperature profile (1st and 2nd part) is
performed automatically.
Manual
No temperature profile is performed, but the control is
performed according to the "manual controlled drying
setpoint". The function is automatically terminated
after 25 days
Comfort
setpoint(710)
Reduced
setpoint(712)
Begin
increase(800)
End increase
(801)
Averaged OT