Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
49
COMMAND
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
FACTORY
SETTING
920
S
Summer comp setp increase
---/1…10°C
4°C
923
S
Flow temp setp min OT 25°C
6…35°C
18°C
924
S
Flow temp setp min OT 35°C
6…35°C
18°C
928 S Room
influence
---/1…100%
80%
932
S
Room temp limitation
---/0…4°C
0.5°C
938
S
Mixing valve decrease
0…20°C
0°C
941
S
Actuator running time
30…650s
120s
945
S
Mixing valve in heating mode
Control ¦ Open
Open
963
S
With prim contr/system pump
No ¦ Yes
No
Heating circuit 2
1010 U
Comfort setpoint
Reduced temp to
35°C
20°C
1012
U
Reduced setpoint
19°C
1014 U
Frost protection setpoint
4°C to Reduced
temp
8°C
1016
S
Comfort setpoint maximum
20…35°C
28°C
1020
I
Heating curve slope
0,1…4
0,5
1021
I
Heating curve displacement
-4,5°C…4,5°C
0°C
1026 S Heating
curve
adaption Off,
on
Off
1030
I
Summer/winter heating limit
8°C…30°C
18°C
1032
S
24-hour heating limit
-10°C…10°C
-2°C
1040
S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C
8°C
1041
I
Flow temp setpoint max
8°C… 95°C
55°C
1050
I
Room influence
1%...100%
50%
1080 S Quick
setback
Off ¦ Down to reduced
setpoint ¦ Down to frost
prot setpoint
Down to reduced
setpoint
1090
S
Optimum start control max
0…360min
180 min
1091
S
Optimum stop control max
0…360min
60 min
1100
S
Reduced setpoint increase start
-30…10°C
---
1101
S
Reduced setpoint increase end
-30…10°C
-5°C
1130
S
Mixer valve boost
0…50°C
0°C
1134 S Actuator
running
time
30…873s 240s
1150
I
Floor curing function
Off
1151
I
Floor curing setpoint manually
0°C…95°C
25°C
1156
I
Floor curing day current
0…32
1157
I
Floor curing day completed
0…32
0
1200
S
Optg mode changeover
Protection mode
Domestic hot water
1610 U Nominal
setpoint
Thc…65°C 55°C
1612
U
Reduced setpoint
8°C….Thc
40°C
1620
I
Release of DHW load
24h/day
Heating circ time pgms
Time program 4/DHW
Off-peak rate
4: Time pgm 4/DHW or
Off-peak rate
Time program
4/DHW
1640
I
Legionella function
Off
Periodically
Fixed weekday
Off
1641
I
Legionella function periodically
1 to 7
7
1642
I
Legionella function weekday
Mon,…Sun
Sunday
Swimming pool
2056
U
Setpoint source heating
8…80
22
Heat pump
2803
S
Overrun time cond pump
0…240s
240
2843
S
Compressor off time min
0…120min
8min
2844
S
Switch-off temp max
8°C… 100°C
75°C
2862
S
Locking time stage 2
0…40min
5min
Summary of Contents for Waterstage WO G112LCT Series