Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
31
2.2.2 Failures With No Error Code
Clear 35: No voltage on Hydraulic Unit
Probable causes:
Power supply fault.
External
causes.
Faulty electrical components.
Check:
1. Check the installation :
- Is the circuit breaker cut off?
- Check the wiring.
2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop):
-
Check for any other electrical device on the same electric circuit which might cause a drop in
voltage.
-
Check for any current leaks.
-
Check for any equipment generating electromagnetic waves which interfere with the
communication between the Hydraulic Unit and the outdoor unit.
3. Check the electrical components:
If all of these checks are unsuccessful, replace Interface PCB.
OK
OK
OK
-
Check that a voltage between AC 198 and AC 264 V exists between terminals 1 and 2 on the
Hydraulic Unit terminal block.
NO
-
Check Interface PCB for :
o
either the fuse (F1).
o
or the varistor (VA1). Fault: overvoltage - external causes - power supply to be
checked).
-
Replace the faulty component (if the varistor is blown, the PCB must be replaced).
YES
Summary of Contents for Waterstage WO G112LCT Series