background image

MAN-I-IPRC14/5-0917

intensity.mx

INSTALLATION

INSTRUCTIONS

IPRC3614KC-5, IPRC4814KC-5, IPRC6014KC-5. 

 

PACKAGE HEAT PUMP

14 SEER 

   3 - 5 TR

220V-3P-60Hz

Summary of Contents for IPRC3614KC-5

Page 1: ...MAN I IPRC14 5 0917 intensity mx INSTALLATION INSTRUCTIONS IPRC3614KC 5 IPRC4814KC 5 IPRC6014KC 5 PACKAGE HEAT PUMP 14 SEER 3 5 TR 220V 3P 60Hz ...

Page 2: ...ing installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION DO NOT DESTROY THIS MANUAL Please read carefully and keep in a safe place for future reference by a service...

Page 3: ...0 0 TROUBLE SHOOTING 21 LIST OF TABLES TABLE 2 1 UNIT CLEARANCE 6 TABLE 6 1 14 SEER HEAT PUMP W WITHOUT ELECTRIC HEAT 12 TABLE 6 2 14 SEER COOLING ONLY W WITHOUT ELECTRIC HEAT 12 TABLE 6 3 14 SEER PHYSICAL DATA 13 TABLE 7 1 SIDE DUCT APPLICATION 14 TABLE 7 2 BOTTOM DUCT APPLICATION 15 TABLE 7 3 REFRIGERANT CHARGE FOR H P SYSTEM 16 TABLE 7 4 REFRIGERANT CHARGE FOR H P SYSTEM 16 TABLE 7 5 REFRIGERAN...

Page 4: ...he use of unauthorized components accessories or devices may adversely affect the operation of the heat pump and may also endanger life and property The manufacturer disclaimer any responsibility for such loss or injury resulting from the use of such unauthorized components accessories or devices WARNING Disconnect all power to the unit before starting maintenance Failure to do so can result in se...

Page 5: ... Manufacturer or distributor will not accept the claims from dealer for any transportation damage 1 1 INSPECTION Refer to Fig 2 2 2 3 for unit physical data and to Table 7 1 for electrical data If components are to be added to a unit they must meet local codes they are to be installed at the dealer s and or the customer s expense Size of unit for proposed installation should be based on heat loss ...

Page 6: ...CAUTION Before lifting make sure the unit weight is distributed equally on the rigging cables so it will lift evenly Units may be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose All panels must be secured in place when the unit is lifted The condenser coils should be protected form rigging cable damage with plywood or other suitable material CAUTION...

Page 7: ...rection Distance in Top Front Rear Right Left Bottom 30 60 18 12 24 0 Duct clearance 1 inch clearance for all sides of air supply duct 1 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 2 The minimum clearance without economizer fresh air damper For distance with Economizer fresh air damper please refer to the relevant Install requ...

Page 8: ... supply air opening Bottom supply air opening Do not drill or install screw in this area Side return air opeing Bottom return air opening Bottom power entry 7 8 and 1 31 32 dia knockout Bottom control entry 7 8 dia knockout Bottom condensate drain 3 4 NPTI T T T T T T T T Screw Screw it off from inside of the unit ...

Page 9: ...if second connection is not used 4 Use a sealing compound on male pipe threads Install the condensate drain line NPT to spill into an open drain A closed return duct system shall be used This shall not preclude use of economizers or ventilation air intake Flexible joints may be used in the supply and return duct work to minimize the transmission of noise When fastening duct work to the side duct f...

Page 10: ...t be kept clean When filter become dirt laden insufficient air will be delivered by the blower decreasing your units efficiency and increasing operation costs and wear and tear on the unit and controls Filters should be checked monthly this is especially important since this unit is used for both heating and cooling 5 0 FILTERS Drain pan A B Drain commutator Drain connector tube Fig 4 1 Removable ...

Page 11: ...uit breakers installed within the unit do not provide over current protection of the supply wiring and therefore may be sized larger than the branch circuit protection Supply circuit power wiring must be 221 F minimum copper conductors only See Electrical Data in this section for ampacity wire size and circuit protector requirements Supply circuit protective devices may be either fuses or HACR typ...

Page 12: ... Field supplied disconnect T h r e e phase power supply Fig 6 2 Typical Field Power Wiring Diagram R G Y W C R G Y W1 W2 C t l o v 4 2 r e m r o f s n a r t THERMOSTAT UNIT CONTROL BOARD THERMINAL STRIP B wire be used with heat pump system only Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire Only required on units with supplemental electric heat Fig 6 1 Typical...

Page 13: ...Tons 2 45A 1 08A 24 9A 048 4 0 208 230 3 60 13 7A 83 1A 060 5 0 21 4A 73A 10 4A 208 230 3 60 036 3 0 MCA 1 Amps Electric Heat Option Max Fuse 2 Breaker 3 Size Amps 16 3A Compressors each OD Fan Motors each Supply Blower Motor RLA LRA MCC FLA FLA Model kW Stages Amps None None EHK 10D 7 5 10 1 20 9 24 1 29 2 33 2 30 35 EHK 15D 11 3 15 2 31 4 36 1 42 4 48 2 45 50 None None EHK 10D 7 5 10 1 20 9 24 1...

Page 14: ... 1 spd 1 1 1 y t i t n a u Q CONDENSER COIL DATA Face area Sq Ft 14 49 17 39 17 39 3 3 7 2 s w o R Fins per inch 20 20 20 Tube diameter 9 32 9 32 9 32 Circuitry type interlaced interlaced interlaced EVAPORATOR COIL DATA Face area Sq Ft 5 15 6 34 6 34 4 4 3 s w o R Fins per inch 16 16 16 Tube diameter 5 16 5 16 5 16 Circuitry type interlaced interlaced interlaced Refrigerant control Orifice Orifice...

Page 15: ... 531 RPM 747 779 811 843 871 903 932 972 Watts 510 500 489 478 464 449 431 405 Amps 2 33 2 3 2 26 2 23 2 19 2 14 2 09 2 02 CFM L S 1837 868 1776 839 1724 814 1647 778 1576 744 1502 709 1413 667 1295 611 RPM 816 845 869 894 918 942 964 992 Watts 615 602 587 575 558 542 522 498 Amps 2 84 2 8 2 76 2 72 2 67 2 63 2 58 2 51 CFM L S 2019 954 1954 923 1892 893 1819 859 1745 825 1656 782 1565 739 1459 689...

Page 16: ...51 1 46 1 41 1 34 1 29 CFM L S 1510 713 1468 693 1420 671 1369 647 1292 610 1218 575 1128 533 934 441 RPM 701 741 779 814 854 892 928 987 Watts 447 438 428 419 408 394 377 347 Amps 1 95 1 92 1 88 1 84 1 8 1 75 1 69 1 59 CFM L S 1705 805 1658 783 1604 758 1549 731 1489 703 1416 669 1321 624 1179 557 RPM 781 815 849 880 908 938 969 1006 Watts 558 547 536 524 511 493 474 445 Amps 2 45 2 41 2 36 2 32 ...

Page 17: ...387 410 434 457 105 200 219 239 258 278 293 308 335 362 385 408 431 454 IPRC3614HP 5 Cooling Mode Cooling Charge Chart Outdoor Ambient Temperature F High Pressure Detected Valve psig Vanne Détecté de Pression Haute en psig Low Pressure Detected Valve psig Vanne Détectée de Pression Basse en psig 60 62 64 66 68 70 72 74 76 78 80 82 135 368 388 403 418 433 448 458 465 472 480 487 494 128 357 375 389...

Page 18: ...ling Charge Chart Cooling Mode Outdoor Ambient Temperature F 60 62 64 66 68 70 72 74 76 78 80 82 135 333 340 347 354 361 370 382 390 398 406 414 426 128 325 332 339 346 353 360 376 383 390 397 404 416 121 318 325 332 339 346 353 367 374 381 388 396 408 114 310 317 324 331 338 347 358 366 374 382 390 402 107 302 309 316 323 330 337 348 355 362 369 379 391 100 295 302 309 316 323 330 338 345 352 359...

Page 19: ...g Mode Outdoor Ambient Temperature F 60 62 64 66 68 70 72 74 76 78 80 82 135 341 353 364 376 388 400 404 408 414 420 426 432 128 337 349 360 372 384 396 400 404 408 412 416 428 121 329 340 351 362 373 384 389 394 399 404 408 420 114 321 331 342 353 364 371 377 383 389 395 401 413 107 313 321 329 337 345 354 362 370 378 386 394 406 100 305 313 321 329 337 345 353 361 369 377 386 398 93 297 305 313 ...

Page 20: ...he compressor will be off When discharge temp is 194 F the compressor will start running High pressure protection When high pressure is 638PSIG the compressor and the outdoor fan motor will stop running When high pressure is 464PSIG the compressor and the outdoor fan motor will start running 3 minutes delay necessary Low pressure protection When low pressure is 21PSIG the compressor and the outdoo...

Page 21: ...OFF Blower fan delay 90 sec OFF Compressor and outdoor fan instant OFF Heater 1 instant OFF 4 way valve instant ON Blower instant ON Compressor and outdoor fan instant ON Heater 1 instant ON Heater 2 instant ON 4 way valve instant OFF Blower fan delay 90 sec OFF Compressor and outdoor fan instant OFF Heater 1 instant OFF Heater 2 instant OFF 8 4 MANUAL DEFROST MODE For HP system only When MANUAL D...

Page 22: ...tes 2 Turn thermostat setting above room temperature Unit should run in HEATING mode After unit has run for a while check the following 1 Are fans running properly 2 Is compressor running correctly 3 Check refrigerant charge 4 Check duct connection and leaks 5 Check tubing and sheet metal rattles See Wiring Diagram for electric connection detail 8 6 Phase sequence protection When connected to the ...

Page 23: ... O R G E L B A C I L P P A S A S E D O C L A C O L D N A C L C C E C C E N C E I D N A E G U A G E M A S E H T E B T S U M E R I W T N E M E C A L P E R E R I W L A N I G I R O S A E P Y T N O I T A L U S N I C N 6 D F C 0 1 M A N U A L D E F R O S T I F M R E D M B L U E L P U R P L E C O M O _ F A N C N 1 0 I N F A N Y O U T C N 1 3 T 3 W 2 Y B Y E L L O W B L U E W 1 R B R V C N 1 5 R V S E T O...

Reviews: