Split system (Single phase and 3-phase type)
26
Maintenance
Document
1544-1
Clear 24: Pressure sensor error
Hydraulic Unit LED: Green 8 flashes / Red 6 flashes
Outdoor Unit LED: 3 flashes
Probable causes:
Connector connection failure
.
Pressure Sensor failure
.
Main PCB failure
.
Check:
2. Check output voltage of Main PCB :
Check voltage of Main PCB (Measure at Main PCB side connector)
1 pin(Red) - 3 pin(Black) DC5V +/- 5%
If the voltage is not correct, replace Main PCB.
OK
3. Check output voltage of Pressure Sensor
Check voltage of Main PCB (Measure at Main PCB side connector)
2 pin(White) - 3 pIn(Black) Voltage is refer to the following graph.
If the voltage is not correct, replace Presure Sensor.
OK
1. Check connection of the Pressure Sensor:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
PRESSURE SENSOR
Voltage [V]
Pressure [MPa]