![Fujitsu Waterstage WO G112LCT Series Maintenance Document Download Page 38](http://html.mh-extra.com/html/fujitsu/waterstage-wo-g112lct-series/waterstage-wo-g112lct-series_maintenance-document_118751038.webp)
Split system (Single phase and 3-phase type)
38
Maintenance
Document
1544-1
2.4.3 Service parts information 3 : Outdoor unit electronic expansion
valve (EEV, EEV(INJ))
Check point 1 : Check connection
Check connection of connector
(Loose connector or open cable)
Check point 2 : Check coil of EEV
Remove connector, check each winding resistance of
coil.
Read wire
Resistance value
White-Red
Yellow-Red
Orange-Red
Blue-Red
46
Ω
+/- 4
Ω
at 20°C
If resistance value is abnormal, replace EEV.
Check point 3 : Check voltage from main PCB
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
Check point 4 : Check noise at start up
Turn on power and check operation noise.
If an abnormal noise does not show, replace Main
PCB.
Check point 5 : Check opening and closing operation of valve
When valve is closed, it has a temp. (Add period)
difference between inlet and outlet.
If it is open, it has no temp. (Add period) difference
between inlet and outlet.
There is no refrigerant flow coming to EEV(INJ) while the liquid injection is inactive. Check whether the liquid
injection is active before executing check point 5 for EEV(INJ).
Check point 6 : Check stainer
Stainer normally does not have temperature difference between inlet and outlet as shown in 1, but if there is a
difference as shown in 2, there is a possibility of inside clogged. In this case, replace stainer.
EXPANSION VALVE
COIL
EXPANSION
VALVE COIL
(INJ)
CLOSE
Example : Hot gas
Pipe (In)
HI TEMP.
Pipe (Out)
Normal TEMP.
OPEN
Example : Hot gas
Pipe (In)
HI TEMP.
Pipe (Out)
HI TEMP.
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
EXPANSION VALVE COIL
EXPANSION VALVE
COIL (INJ)
Single phase :
3-phase :
Summary of Contents for Waterstage WO G112LCT Series
Page 2: ......