Powering on sequence
1
Power on of all the server UPS units
2
Server startup
The server OS startup is suspended until the ETERNUS DX startup is complete (*1).
3
Issuance of command to turn on the ETERNUS DX from the power synchronized unit
4
ETERNUS DX startup
*1: The server must be set to suspend server OS startup until the ETERNUS DX startup is complete.
Powering off sequence
1
Shutdown of all the servers
2
Shutdown of all the server UPS units
3
Issuance of command to turn off the ETERNUS DX from the power synchronized unit
4
ETERNUS DX shutdown
4. Connection Configuration
Power Synchronized Connections
164
FUJITSU Storage ETERNUS DX500 S4/DX600 S4, ETERNUS DX500 S3/DX600 S3 Hybrid Storage Systems Design Guide (Basic)