![Fuji Electric frenic mini series User Manual Download Page 8](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845008.webp)
v
Control circuit
wiring length
When using remote control, limit the wiring length between the inverter
and operator box to 20 m or less and use twisted shielded cable.
Wiring length
between inverter
and motor
If long wiring is used between the inverter and the motor, the inverter will
overheat or trip as a result of overcurrent (high-frequency current flowing
into the stray capacitance) in the wires connected to the phases. Ensure
that the wiring is shorter than 50 m. If this length must be exceeded, lower
the carrier frequency or mount an output circuit filter (OFL).
Wiring size
Select cables with a sufficient capacity by referring to the current value or
recommended wire size. For details about the ambient temperature and
wire types, refer to Chapter 6, Section 6.2 "Selecting Wires and Crimp
Terminals" and Appendices, App. G "Allowable Current of Insulated
Wires."
Wiring type
Do not use multicore cables.
Wiring
Grounding
Securely ground the inverter using the grounding terminal.
Driving general-
purpose motor
Select an inverter according to the applicable motor ratings listed in the
standard specifications table for the inverter.
When high starting torque is required or quick acceleration or deceleration
is required, select an inverter with a capacity one size greater than the
standard. Refer to Chapter 7, Section 7.1 "Selecting Motors and Inverters"
for details.
Selecting
inverter
capacity
Driving special
motors
Select an inverter that meets the following condition:
Inverter rated current > Motor rated current
Transpor-
tation and
storage
When transporting or storing inverters, follow the procedures and select locations that meet the
environmental conditions listed in the FRENIC-Mini Instruction Manual, Chapter 1, Section 1.3
"Transportation" and Section 1.4 "Storage Environment."
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...