4.2 Drive Frequency Command Generator
4-3
Chap. 4
BLOC
K DI
AGR
A
MS F
O
R
CONT
ROL
LOGIC
Figure 4.1 shows the processes that generate the final drive frequency command from the frequency
settings given by various means and those switched/modified by function codes. If PID process control
takes effect (J01=1 or 2), the drive frequency generation will differ from that shown in this diagram. (Refer
to Section 4.8 "PID Frequency Command Generator.")
Additional and supplemental information is given below.
- Frequency settings using the / keys on the keypad may take a different format by means of the data
setting for function code E48. Refer to function code E48 in Chapter 9 "FUNCTION CODES" for
details.
- [C1] input as a frequency settings signal will always be interpreted as "0" when the current input signal
terminal [C1] is specified for the thermistor (H26 = 1).
- Settings for both gain and bias will take effect concurrently only for frequency setting 1 (F01). For
frequency setting 2 (C30) and auxiliary frequency settings 1 and 2 (E60 to E62), only the gain will take
effect.
- Gain for the built-in potentiometer cannot be changed by any function code or other means.
- Switching between normal and inverse operation is only effective for frequency setting from the analog
input signal (terminal [12], [C1] or built-in potentiometer). Frequency settings from the / keys are
only valid for normal operation.
- The command formats for frequency settings by S01 and S05 for the communications link facility take a
different form, as follows:
- S01: the setting range is –32768 to +32768, where the maximum output frequency is obtained at
±
20000.
- S05: the setting range is 0.00 to 655.35 Hz in 0.01 Hz step, or 0.1 Hz step for over 600 Hz.
- Priority level for setting for S01 is higher than that for S05. If a value other than 0 is set for S01,
then the data set to S01 will take effect. If S01 = 0, then the setting for S05 will take effect.
- Refer to the user's manual of RS485 communication for details.
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...