8-18
<
Signals assigned at transistor output terminal
Cla
ssifi-
cat
ion
Signal
Signal
name
Functions
Related
function
codes
(RUN)
Inverter running
Comes ON when the output frequency is higher than
starting frequency.
E20 = 0
(RUN2)
Inverter output on Comes ON when the main circuit (gate) is turned on.
E20 =
35
(FAR)
Speed/freq.
arrival
Comes ON when the motor speed reaches the set
frequency. (Condition: Run command is ON.)
(Hysteresis width (fixed): 2.5 Hz)
E20 = 1
(FDT)
Speed/freq.
detection
Comes ON when the output frequency is above the
detection level and goes OFF when below the
detection level.
(Hysteresis width (fixed): 1.0 Hz)
E20 = 2
E31
(LU)
undervoltage
detection
Comes ON when the inverter stops its output because
of undervoltage while the run command is ON.
E20 = 3
(IOL)
Inverter output
limit (limit on
current)
Comes ON when the inverter is limiting the current.
E20 = 5
F43,
F44
(IPF)
Auto-restarting
Comes ON during auto-restarting operation (after
instantaneous power failure and until completion of
restart).
E20 = 6
F14
(OL)
Overload early
warning (for
motor)
Comes ON when the calculated value of electronic
thermal relay is higher than the preset alarm level.
E20 = 7
F10 to
F12
(TRY)
Auto-resetting
Comes ON during
auto-resetting mode.
E20 =
26
H04,
H05
Sig
na
ls assign
ed at tran
sistor ou
tp
ut
termin
al
(LIFE)
lifetime alarm
Outputs alarm signal according to the preset lifetime
level.
E20 =
30
H42,
H43
(OLP)
Overload
preventive control
Comes ON during inverter control for avoiding
overload.
E20 =
36
H70
(ID)
Current detection
Comes ON when a current larger than the set value
has been detected for the timer-set time.
E20 =
37
E34,
E35
(IDL)
Small current
detection
Comes ON when a current smaller than the set value
has been detected for the timer-set time.
E20 =
41
E34,
E35
(ALM)
Alarm relay (for
any fault)
Alarm signal is output as the transistor output signal.
E20 =
99
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...