9.2 Details of Function Codes
9-43
Chap. 9
FUNCTI
ON C
O
DE
S
C30
Frequency Command 2
(Refer to F01.)
For details on frequency command 2, refer to the description for function code F01.
C32
Analog Input Adjustment (Gain for terminal input [12])
(Refer to F18.)
C34
Analog Input Adjustment (Gain reference point for terminal input [12])
(Refer to F18.)
C37
Analog Input Adjustment (Gain for terminal input [C1])
(Refer to F18.)
C39
Analog Input Adjustment (Gain reference point for terminal input [C1])
(Refer to F18.)
For details on adjusting the analog inputs, refer to the description for function code F18.
C33
Analog Input Adjustment (Filter for terminal input [12])
C38
Analog Input Adjustment (Filter for terminal input [C1])
C33 (voltage input) and C38 (current input) set the time constant of the filter for the analog
input on terminal [12] and [C1], respectively.
- Data setting range: 0.00 to 5.00 (sec.)
- The larger the time constant, the slower the response. Set the time constant suitable to the
load with consideration given to the system response. When the analog input fluctuates
due to electric noise, first remove the noise factor or protect the input from noise by
electric means (grounding the shield, ferrite core or capacitor). After that, increase the
time constant if you cannot remove the noise factor to a sufficiently degree.
C50
Bias (Bias reference point for frequency command 1)
(Refer to F18.)
For details of setting the bias reference point for frequency command 1, refer to the
descriptions of function code F18.
C51
Bias (Bias for PID command 1)
C52
Bias (Bias reference point for PID command 1)
These function codes modify the analog input of the PID process command 1 by gain and
bias, enabling defining the arbitrary relationship between the analog input and PID process
command to be arbitrarily defined.
The actual setting is the same as that of function code F18. For details, refer to the
description of function code F18.
Note that function codes C32, C34, C37 and C39 are shared by the drive
frequency commands.
Bias (C51)
- Data setting range: -100.00 to 100.00 (%)
Bias reference point (C52)
- Data setting range: 0.00 to 100.00 (%)
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...