9.2 Details of Function Codes
9-11
Chap. 9
FUNCTI
ON C
O
DE
S
9.2 Details of Function Codes
This section provides a detailed description of the function codes available for the FRENIC-Mini
series of inverters. In each code group, its function codes are arranged in an ascending order of the
identifying numbers for ease of access. Note that function codes closely related each other for the
implementation of an inverter's operation are detailed in the description of the function code having
the youngest identifying number. Those related function codes are indicated in the title bar as shown
below.
F01
Frequency Command 1
Refer to C30.
9.2.1
F Codes (Fundamental Functions)
F00
Data Protection
Specifies whether function code data is to be protected from being accidentally changed by
keypad operation. If data protection is enabled (F00 = 1),
or key operation to change
data is disabled so that no function code data, except F00 and H03 data, can be changed
from the keypad.
Even if F00 = 1, function code data can still be changed using the communications
facility.
Set F00 to:
To do this
Setting procedure
0
Disable data protection.
1
Enable data protection.
Press the
and
keys or
and
keys
simultaneously to change data from 1 to 0 or from
0 to 1, respectively. Press the
key to save the
change.
F01
Frequency Command 1
Refer to C30.
Selects the devices to set the set frequency 1 for driving the motor.
Set F01 to:
To do this
0
Enable the
and
keys on the built-in keypad. (Refer to Chapter 3
"OPERATION USING THE KEYPAD.")
1
Enable the voltage input to terminal [12] (0 to 10 VDC, maximum output
frequency obtained at 10 VDC).
2
Enable the current input to terminal [C1] (4 to 20 mA, maximum output
frequency obtained at 20 mA).
3
Enable the sum of voltage and current inputs to terminals [12] and [C1]. See
the two items listed above for the setting range and maximum frequencies.
Note: If the sum exceeds the maximum output frequency, the maximum output
frequency will apply.
4
Enable the built-in potentiometer (POT). (Maximum frequency obtained at full
scale of the POT)
There are other frequency setting means (such as the communications facility,
multi-step frequency and etc.) with higher priority than that of F01. Refer to
Chapter 4, Section 4.2 "Drive Frequency Command Generator" for more details.
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...