![Fuji Electric frenic mini series User Manual Download Page 40](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845040.webp)
3.3 Programming Mode
3-9
Chap. 3
OP
ERA
T
ION US
ING
THE
K
EYP
AD
Limiting menus to be displayed
The menu-driven system has a limiter function (specified by function code E52) that limits menus to
be displayed for the purpose of simple operation. The factory default is to display Menu #1 "Data
setting" only, allowing no switching to any other menu.
Function Code E52 – Keypad (Mode Selection)
Function code data (E52)
Menus selectable
0: Function code data setting mode
Menu #1 "Data setting" (factory default)
1: Function code data check mode
Menu #2 "Data checking"
2: Full-menu mode
Menu #1 through #6 (#7*)
* Menu #7 appears only when the remote keypad (option) is set up for use.
If the full-menu mode is selected, pressing the or key will cycle through menus.
With the
key, you may select the desired menu. Once all of the menus have been cycled
through, the display will return to the first menu.
3.3.1 Setting the Function Codes--"Data setting"
Menu #1 "Data setting" in Programming mode allows you to set function codes for making the
inverter functions match your needs.
The table below lists the function codes available in the FRENIC-Mini. The function codes are
displayed on the LED monitor on the keypad as shown below.
Table 3.4 List of FRENIC-Mini Function Codes
Function code group
Function code
Function
Description
F codes
(Fundamental functions)
F00 to F51
Basic functions
To be used for basic motor running.
E codes
(Extension terminal
functions)
E01 to E99
Terminal
functions
To be used to select the functions of
the control circuit terminals.
To be used to set functions related
to the LED monitor display.
C codes
(Control functions of
frequency)
C01 to C52
Control functions
To be used to set application
functions related to frequency
settings.
P codes
(Motor parameters)
P02 to P99
Motor parameters
To be used to set specific
parameters for the motor capacity,
etc.
H codes
(High performance
functions)
H03 to H98
High level
functions
To be used for high added value
functions and complicated control,
etc.
J codes
(Application functions)
J01 to J06
Application
functions
To be used for PID control.
y codes
(Link functions)
y01 to y99
Link functions
To be used for communications.
Refer to Chapter 9 "FUNCTION CODES" for details on the function codes.
Function code group
ID number in each function code group
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...