![Fuji Electric frenic mini series User Manual Download Page 140](http://html1.mh-extra.com/html/fuji-electric/frenic-mini-series/frenic-mini-series_user-manual_2341845140.webp)
8.4 Terminal Specifications
8-15
Chap. 8
SPECIFIC
A
T
ION
S
Cla
ssifi-
cat
ion
Command
Command name
Functions
Related
function
codes
(BX)
Coast-to-stop
command
[X3] - [CM] ON:
The inverter output is stopped
immediately and the motor
will coast-to-stop.
(No alarm signal will be output.)
(e.g.) Assigns the command (BX) to terminal [X3].
E03 = 7
(RST)
Alarm reset
[X1] - [CM] ON:
Alarm status is reset.
(ON signal should be held for 0.1 s or longer.)
(e.g.) Assigns the command (RST) to terminal [X1].
E01 = 8
(THR)
Alarm from
external
equipment
[X2] - [CM] OFF:
The inverter output is stopped
and the motor coasts-to-stop.
Alarm signal for the alarm code
OH2
will be output.
(e.g.) Assigns the command (THR) to terminal [X2].
E02 = 9
(JOG)
Jogging operation [X3] - [CM] ON:
Jogging operation is effective.
(FWD) or (REV) ON: The inverter runs the motor
with jogging frequency.
(e.g.) Assigns the command (JOG) to terminal [X3].
E03 =
10
C20 =
0.00 to
400.0
Hz
H54 =
0.00 to
3600 s
(Hz2/Hz1)
Freq. set2/
Freq. set1
[X1] - [CM] ON:
Frequency command 2 is
effective.
(e.g.) Assigns the command (Hz2/Hz1) to terminal
[X1].
E01 =
11
F01 = 0
to 4
C30 = 0
to 4
(WE-KP)
Write enable for
keypad
[X2] - [CM] ON:
The function code data can be
changed from the keypad.
(Data can be changed when this function is not
allocated.)
(e.g.) Assigns the command (WE-KP) to terminal
[X2].
E02 =
19
C
omma
nd
s assi
gne
d
on
di
gi
ta
l i
nput
te
rmi
nal
s
(Hz/PID)
PID control
cancel
[X3] - [CM] ON:
The PID control is cancelled,
and the set frequency is set by
the Multi-step frequency,
keypad or analog input.
(e.g.) Assigns the command (Hz/PID) to terminal
[X3].
For details about J01 to J06 data, refer to Chapter 9,
"FUNCTION CODES."
E03 =
20
J01 to
J06
F01 = 0
to 4
C30 = 0
to 4
(IVS)
Inverse mode
changeover
[X1] - [CM] ON:
Normal mode operation or
inverse mode operation can be
changed in the frequency
command and PID control.
(e.g.) Assigns the command (IVS) to terminal [X1].
E01 =
21
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...