8-30
Name
Description
LED
monitor
displays
Alarm
output
[30A,B,C]
Related
function
code
Overload
protection
Stops the inverter output if the Insulated Gate
Bipolar Transistors (IGBT) internal temperature
calculated from the output current and cooling fan
temperature detection is over the preset value.
0LU
Yes
---
In the following cases, the inverter stops running
the motor to protect the motor in accordance with
the electronic thermal function setting.
Electronic
thermal
overload
relay
• Protects general-purpose motors over the entire
frequency range.
• Protects inverter motors over the entire frequency
range.
* The operation level and thermal time constant
can be set.
0L1
Yes
F10
F11, F12
PTC
thermistor
A PTC thermistor input stops the inverter output for
motor protection.
A PTC thermistor is connected between terminals
[C1] and [11], and a 1 k
Ω
=
external resistor is
connected between terminals [13] and [C1].
0H4
Yes
H26,
H27
M
ot
or pro
tectio
n
Overload
early
warning
Outputs a preliminary alarm at a preset level before
the motor is stopped by the electronic thermal
function for the purpose of protecting the motor.
---
---
E34,
E35
Stall prevention
Operates when the current limiting is active.
Current limiting: Operates if the current limiting set
in the hardware is exceeded by the inverter's output
current, avoiding tripping of the inverter (during
constant speed operation or during acceleration).
---
---
H12
External alarm
input
Stops the inverter output with an alarm through the
digital input signal (THR).
0H2
Yes
E01 to
E03,
E98,
E99
Alarm relay
output
(for any fault)
The inverter outputs a relay contact signal when the
inverter issues an alarm and stops the inverter
output.
< Alarm Reset >
The alarm stop state is reset by pressing the
key
or by the digital input signal (RST).
< Saving the alarm history and detailed data >
The information on the previous 4 alarms can be
saved and displayed.
---
Yes
E20,
E27,
E01 to
E03,
E98,
E99
Memory error
The inverter checks memory data after power-on
and when the data is written. If a memory error is
detected, the inverter stops its output.
E 1
Yes
---
"---": Not applicable.
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...