9-4
Code
Name
Data setting range
Incre-
mental
unit
Unit
Change
when
running
Data
copy
Default
setting
F37 Load Selection/
Auto Torque Boost/
Auto Energy Saving
Operation
0:
Torque reversely proportional to the square
of speed
1:
Constant torque load
2:
Auto-torque boost
3:
Auto-energy saving operation
(Variable torque load during acceleration
and deceleration)
4:
Auto-energy saving operation
(Constant torque load during acceleration
and deceleration)
5:
Auto-energy saving operation
(Auto-torque boost during acceleration
and deceleration)
—
—
N
Y
1
F43 Current Limiter
(Operation condition)
0:
Disabled
1:
In constant speed
(Disabled during acceleration and
deceleration)
2:
At acceleration and in constant speed
(Disabled during deceleration)
—
—
Y
Y
0
F44
(Limiting level) 20 to 200 (The data is interpreted as the rated
output current of the inverter for 100 %.)
1
%
Y
Y
200
F50 Electronic Thermal
Overload Relay
(for braking resistor)
(Discharging capability)
0: (To be set for braking resistor built-in type)
1 to 900
999: (Disabled)
1
kWs
Y
Y
999/0
F51
(Allowable loss) 0.000: Applied for built-in braking resistor,
0.001 to 50.000
0.001 kW
Y
Y
0.000
Note: The default setting of function code F50 is 999 for standard models, and 0 for braking resistor built-in type.
E codes: Extension Terminal Functions
Code
Name
Data setting range
Incre-
mental
unit
Unit
Change
when
running
Data
copy
Default
setting
E01 Terminal Command
Assignment to:[X1]
—
—
N
Y
0
E02
[X2]
—
—
N
Y
7
E03
[X3]
To assign a negative logic input to a terminal,
set the value of 1000s shown in ( ) in the table
below to the function code.
0:
(1000) Multi-step frequency selection
(0 to 1 steps)
(SS1)
1:
(1001) Multi-step frequency selection
(0 to 3 steps)
(SS2)
2:
(1002) Multi-step frequency selection
(0 to 7 steps)
(SS4)
4:
(1004) ACC/DEC time selection
(2 steps)
(RT1)
6:
(1006) 3-wire operation stop command
(HLD)
7:
(1007) Coast-to-stop command
(BX)
8:
(1008) Alarm reset
(RST)
9:
(1009) Alarm from external equipment (THR)
10: (1010) Ready for jogging
(JOG)
11: (1011) Frequency command 2 or 1
(Hz2/Hz1)
19: (1019) Enable editing of function codes
from keypad
(WE-KP)
20: (1020) Disable PID control
(Hz/PID)
21: (1021) Switch normal/inverted driving
(IVS)
24: (1024) Select link operation
(RS485 (standard), BUS (option))
(LE)
33: (1033) Reset PID integral and differential
components
(PID-RST)
34: (1034) Hold PID integral component
(PID-HLD)
—
—
N
Y
8
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...