9-24
F27
Motor Sound (Tone)
Set F27 to:
To set the tone
level
0
0
1
1
2
2
Changes the motor running sound tone. This setting is
effective when carrier frequencies set to function code
F27 is 7 kHz or lower. Changing the tone level may
reduce the high and harsh running noise from the
motor.
3
3
F30
Terminal [FMA] (Gain to output voltage)
F31
Analog Output Signal Selection for [FMA] (Monitor object)
F31 allows you to output monitored data (such as the output frequency or output current) to
terminal [FMA] as an analog data that can be adjusted with F30 for the meter scale.
Adjusting the output voltage level (F30)
Adjust the output voltage level within the range of 0 to 200%, supposing the monitored
amount of the monitor selected with function code F31 as 100%.
- Data setting range: 0 to 200 (%)
Meter scale
Selecting object to be monitored (F31)
Select the output to terminal [FMA] for monitoring.
Set F31 to:
To monitor the following:
Based on the following
defined as 100% (full-scale)
0
Output frequency 1
(before slip compensation)
Maximum output frequency
1
Output frequency 2
(after slip compensation)
Maximum output frequency
2
Output current
Two times the inverter's rated output current
3
Output voltage
200 V class: 250 V
400 V class: 500 V
6
Input power
Two times the inverter's rated output capacity
7
PID feedback amount
Feedback amount is 100%
9
DC link circuit voltage
200 V class: 500 V
400 V class: 1000 V
14
Test output (+)
10 V
Summary of Contents for frenic mini series
Page 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Page 2: ...Compact Inverter User s Manual...
Page 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Page 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Page 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Page 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Page 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Page 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Page 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Page 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Page 135: ...8 10...
Page 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Page 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...