IMPORTANT!
To control the inverter via DRM, a Fronius DRM interface (item
number 4,240,005) is required in the inverter.
Installation is described in the Installation Instructions for the Fronius DRM
interface. The Installation Instructions for the Fronius DRM interface are avail-
able on the Fronius homepage at the following link:
http://www.fronius.com/QR-link/4204102292
Mode
Description
Information
De-
fault
pin
DRM0
Inverter disconnects itself
from the grid
Open grid relay
REF GEN
Closed
FDI
COM LOAD
closed
or
combinations of invalid
DRM1 - DRM8
FDI
DRM1
-P
nom
≤ 0% without discon-
nection from the grid
limits effective power input
6
DRM2
-P
nom
≤ 50%
limits effective power input
7
DRM3
-P
nom
≤ 75% & +Q
rel
* ≥ 0%
limits effective power input
and
sets the reactive power
8
DRM4
-P
nom
≤ 100%
Normal operation without
limitation
9
DRM5
+P
nom
≤ 0% without discon-
nection from the grid
limits effective power out-
put
6
DRM6
+P
nom
≤ 50%
limits effective power out-
put
7
DRM7
+P
nom
≤ 75% & -Q
rel
* ≥ 0%
limits effective power out-
put
and
sets the reactive power
8
DRM8
+P
nom
≤ 100%
Normal operation without
limitation
9
FDI
on the Fronius DRM inter-
face
*
The values for Q
rel
can be set in the PSC Editor menu item.
97
EN
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......