Code
Description
Behaviour
Remedy
417
Hardware ID problem
The inverter will auto-
matically attempt to
connect again and, if
possible, will resume
feeding energy into the
grid.
Update inverter firm-
ware; *)
420
Unable to communicate with sys-
tem monitoring
425
Unable to communicate with the
power stage set
426 -
427
Possible hardware fault
431,
432
Software problem
The inverter is not feed-
ing any energy into the
grid.
Perform AC reset
(switch automatic
circuit breaker off
and on again); up-
date inverter firm-
ware; *)
436
Functional incompatibility (one or
more PC boards in the inverter are
not compatible with each other, e.g.
after a PC board has been re-
placed)
The inverter will auto-
matically attempt to
connect again and, if
possible, will resume
feeding energy into the
grid.
Update inverter firm-
ware; *)
437
Power stage set problem
438
Functional incompatibility (one or
more PC boards in the inverter are
not compatible with each other, e.g.
after a PC board has been re-
placed)
The inverter will auto-
matically attempt to
connect again and, if
possible, will resume
feeding energy into the
grid.
Update inverter firm-
ware; *)
445
-
Compatibility error (e.g. due to
replacement of a PC board)
-
Invalid power stage set config-
uration
The inverter is not feed-
ing any energy into the
grid.
Update inverter firm-
ware; *)
447
Insulation fault (PV or battery)
The inverter is not feed-
ing any energy into the
grid.
*)
450
Guard cannot be found
451
Memory error detected
The inverter will auto-
matically attempt to
connect again and, if
possible, will resume
feeding energy into the
grid.
*)
452
Communication error between the
processors
453
Grid voltage and power stage set
are incompatible
454
Grid frequency and power stage set
are incompatible
456
Anti-islanding function is no longer
being implemented correctly
457
Grid relay is sticking or the neutral
conductor ground voltage is too
high
The inverter is not feed-
ing any energy into the
grid.
Check the grounding
(the neutral con-
ductor ground
voltage must be less
than 30 V); *)
126
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......