Code
Description
Behaviour
Remedy
509
No energy fed into the grid
in the past 24 hours
Warning message is
shown on the display
Acknowledge status code;
check whether all the conditions
for the problem-free feeding of
energy into the grid have been
met (e.g. are the solar modules
covered with snow?); **)
515
Unable to communicate
with filter
Warning message on
the display
*)
516
Unable to communicate
with the data storage unit
Data storage unit
warning message
*)
517
Power derating caused by
excessively high temperat-
ures
When power derat-
ing occurs, a warning
message is shown on
the display.
If necessary, purge cooling air
openings and heat sink;
fault is rectified automatically;
**)
519
Unable to communicate
with the data storage unit
Data storage unit
warning message
*)
520
No energy fed into the grid
by the PV in the past 24
hours
Warning message is
shown on the display
Acknowledge status code;
check whether all the conditions
for the problem-free feeding of
energy into the grid have been
met (e.g. are the solar modules
covered with snow?); *)
522
DC low (PV). No PV
voltage available.
Warning message on
the display
In the case of hybrid systems,
this message appears overnight
if no photovoltaics are connec-
ted to the Fronius Symo Hybrid
or in standby mode; *)
558,
559
Functional incompatibility
(one or more PC boards in
the inverter are not com-
patible with each other,
e.g. after a PC board has
been replaced)
Warning message on
the display
Update inverter firmware; *)
560
Power derating caused by
overfrequency
Displayed when grid
frequency becomes
excessively high. The
power is reduced.
As soon as the grid frequency is
back within the permissible
range and the inverter has re-
turned to normal operation, the
fault is rectified automatically;
**)
567
Power derating caused by
overvoltage
Displayed when grid
voltage becomes ex-
cessively high. The
power is reduced.
As soon as the grid voltage is
back within the permissible
range and the inverter has re-
turned to normal operation, the
fault is rectified automatically;
**)
573
Power derating caused by
excessively low temperat-
ures
When power derat-
ing occurs, a warning
message is shown on
the display.
Fault rectified automatically; **)
*) If the status code is displayed all the time: notify a Fronius-trained service en-
gineer
**) If this status code keeps recurring, contact your system engineer.
128
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......