Operating Manual BKS600A
29
9.5
Description of the Parameters BKS600A
The parameter changing mode is activated by pressing the
PARA
↵
key for 3 seconds. The
module
Params BKS 600 1
is then searched with the
↑
↓
keys and selected with the
PARA
↵
key (ref. also to fig. 22).
Control mode
Use:
This parameter defines on which side of the material web the sensors are
used. When center guiding there must be sensors on both sides of the web.
Range:
Edge left, Edge right, Center
Default:
Edge
left
Dead band
Use:
This parameter declares how great the tolerance for the web position will
be. The web position is adjusted only when the difference between
reference and feedback position is greater than the dead band value.
„0.3mm dead band“ means a tolerance of ±0.3mm.
Range:
0.0
to
5.0
Default:
0.0
Increment:
0.1
Unit:
[mm]
Device active
Use:
If multiple web guiding control loops are operated with a single electronic
unit, it may be helpful for trouble shooting to disable a web guiding control
loop. This is done with this parameter.
Range:
Yes,
No
Default:
Yes
Analog output
Use:
This parameter defines what signal is provided at the analog output. If set
to
Controller output
an actuator with analog signal can be operated instead
of an FMS steering frame (i.e. hydraulic valve; ref. to parameter
Output
config.
). If set to
Feedback sensor
the actual web position is provided at
the output in the automatic mode.
Range:
Feedback sensor, Controller output
Default:
Feedb.
sens.
Scale feedback
Use:
If
parameter
Analog output
is set to
Feedback sensor
, this parameter
defines the mm value the full signal range (±10V / 0...10 V / 0...20mA /
4...20mA; ref. to parameter
Output config.
) is referring to.
Range:
0.1
to
3200.0
Default:
5.0
Increment:
0.1
Unit:
[mm]