Operating Manual BKS600A
30
Output manual
Use:
If
parameter
Analog output
is set to
Controller output
, this parameter
defines the signal value which drives the actuator when using the manual
mode. If the sign is changed, the polarity of the analog output signal is
changed too. „5%“ means 5% of the full signal range (±10V / 0...10 V /
0...20mA / 4...20mA; ref. to parameter
Output config.
)
Range:
-100.0
to
+100.0
Default:
+5.0
Increment:
0.1
Unit:
[%]
Offset output
Use:
If
parameter
Analog output
is set to
Controller output
and the actuator is
moving although the control unit gives no signal to move, the faulty
movement can be compensated here. This ensures that the actuator will
stay if no movement signal is given.
This parameter can be adjusted also while automatic mode is active.
Range:
–200 to
200
Default:
0
Increment:
1
Unit:
[Digit]
Limit output
Use:
If
parameter
Analog output
is set to
Controller output
, this parameter
defines the maximum output signal. „80%“ means to 80% of the full signal
range (±10V / 0...10 V / 0...20mA / 4...20mA; ref. to parameter
Output
config.
)
This parameter can be adjusted also while automatic mode is active.
Range:
1
to
100
Default:
100
Increment:
1
Unit:
[%]
P value output
Use:
If
parameter
Analog output
is set to
Controller output
, this parameter
defines the P component of the PI controller.
This parameter can be adjusted also while automatic mode is active.
Range:
0.01
to
320.00
Default:
1.00
Increment:
0.01
Unit:
[-]
I value output
Use:
If
parameter
Analog output
is set to
Controller output
, this parameter
defines the I component of the PI controller.
This parameter can be adjusted also while automatic mode is active.
Range:
0.01
to
320.00
Default:
1.00
Increment:
0.01
Unit:
[s]