Operating Manual BKS600A
43
Setting the analog output (jumper)
Channel 1
(main board)
Channel 2...4
(subprint)
Analog output
0...10V
Analog output
±10V
(default)
J1100
J100
2-3
1-2
Setting the sensor excitation (solder bridges)
Channel 1
(main board)
Channel 2...4
(subprint)
Sensor excitation
24VDC
(default)
Sensor excitation
10VDC
J1200
J200
2-3
2-3
J1201
J201
closed
closed
J1202
J202
closed
open
J1203
J203 open
closed
J1204
J204
closed
open
J1205
J205 open
closed
Setting the sensor signal (solder bridges)
Channel 1
(main board)
Channel 2...4
(subprint)
Sensor signal
0...10V
(default)
J1208
J208 open
J1209
J209 open
J1210
J210
closed
J1211
J211
closed
J1212
J212 open
Setting to 4 wire or 6 wire circuit (solder bridges)
Channel 1
(main board)
Channel 2...4
(subprint)
4 wire circuit
(default)
J1206
J206
closed
J1207
J207
closed
Note
The jumpers and solder bridges are normally factory set and need no customization.