User manual D030-P Batch Controller
3 –
I
NSTALLATION
I
NSTRUCTIONS
10
FW-D030-P-MAN-EN-V0102_02
Connector Types and Wiring Sizes
The following connector types are fitted. Wires are connected using a flat head screw driver:
Classic COMBICON
A screw connector with 5.08mm pitch, suitable for 0.2—2.5mm2 or AWG
24—12 wire. Max. torque 0.5Nm.
Power Supply Wiring
Below section describes the available power supply types for the D030-P. Which types are
available in your particular D030-P depends on the ordering code.
Battery equipped models switch their internal battery off when an external supply is active.
The following power supply options are available:
• Battery powered. see "Battery powered type PB" on page 10 for details.
• Externaly powered, see ""External Power Supply wiring" on page 10" for details.
Battery powered type PB
Type PB is internally battery powered and does not require any external wiring.
When power supply PX is available (see below) the internal battery is switched off. This extends
battery life and guarantees higher availability during power outages.
• A healthy battery has a life expectancy of several years, depending on its use and
configuration settings. For details see "Battery life" on page 31.
• When installing verify that the battery is in good working condition by running the power-up
sequence on page iv of this manual. If the battery needs to be replaced follow the battery
replacement instructions delivered with the new battery.
External Power Supply wiring
The D030-P can be equipped with a power supply, type PX or PD.
• For type PX or PD DC your D030-P must be equipped with a 6 pole connector.
Type PD can also power your flowmeter in the field, see "Power wiring type PD" on page 11 for
details.
Figure 7:
Voltage switch positions
8.2V
12V
24V
A
B
A
B
A
B
A
B
A
or
B
A
B
Note:
• Type PX < 16V does not foresee in the (optional) backlight power; see "Backlight" on
page 12.
• The internal battery is on standby, when external power is supplied. Note that the
internal battery
cannot
be used to power a flowmeter with 8.2V (pin S4)!
Caution:
The D030-P and it’s field devices are functionally isolated to a maximum of 500V!