User manual D030-P Batch Controller
C
ONFIGURING
THE
D030-P – 4
FW-D030-P-MAN-EN-V0102_02
25
S
ETUP
M
ENU
4 — P
OWER
M
ANAGEMENT
Below setup options are smart power management functions to set the optimum between the
response time of the unit and the (optional) battery life time.
SETUP
41
LCD New
LCD New defines the display update frequency when the D030-P is unmanned (no buttons
pressed).
A slow update frequency extends battery life but reduces display response.
The following options are available:
fast - 1 sec - 3 sec - 15 sec - 30 sec - off
SETUP
42
Battery Mode
Battery Mode initiates a power down to prevent battery drainage during transport and/or
storage. Two settings are provided:
shelf - operate
S
ETUP
M
ENU
5 — F
LOWMETER
Below setup items adjust the D030-P to accomodate to your type of flowmeter signal.
SETUP
51
Signal
Signal defines the type of flowmeter pickup signal for this input. You can choose one of the
following flowmeter signal types:
NPN - NPN-LP - REED - REED-LP - PNP - PNP-LP - NAMUR - COIL HI - COIL LO - ACT_8.1 -
ACT_12 - ACT_24
For configuration details see "Flowmeter Pickup Signal Types Supported" on page 33.
Example:
• Expected battery life with a coil pick-up, 1KHz. pulses and
fast
update: about 2
years.
• Expected battery life with a coil pick-up, 1KHz. pulses and
1 sec
update: about 5
years.
Notes:
• This setting does not impact the data processing speed. Irrespective of this setting,
field data is always processed at at high speed.
• When manned (buttons pressed) the display switches to
fast
for 30 seconds.
• When
off
is selected press a button to activate the display.
shelf
Puts the D030-P in standby to allow storage for years with minimal battery drainage. The D030-P will
not function but saved totals and settings remain stored in this mode.
Press
START
twice to awake an D030-P in
standby
.
operate
Powers up the D030-P and performs a self test, after which it will switch to operator mode.