User manual D030-P Batch Controller
4 –
C
ONFIGURING
THE
D030-P
24
FW-D030-P-MAN-EN-V0102_02
SETUP
15
Batch Maximum
Batch Maximum limits the operator to enter a new preset-value which is more as the entered
batch maximum.
The following options are available:
X,XXX,XXX quantity
S
ETUP
M
ENU
2 — O
VERRUN
Overrun can occur at the end of the batch process, as a result of slowness of a valve / pump.
Consequently, the accuracy is less. With this function, the D030-P analyses the actual overrun
characteristic after every batch. This information is used to correct the overrun automatically.
SETUP
21
Overrun
For an accurate overrun correction, it is necessary that the batch controller meets certain
technical demands, such as "high resolution" and shows no "false" overrun due to a slow update
time.
Do not enable this function if the flow meter does not meet these technical demands.
disable - enable
SETUP
22
Time
The overrun characteristic of the system will be analyzed during a certain time after the batch. In
this way, false signal generated through leakage are eliminated.
Enter here the expected time needed by the system to stop a batch.
It is advisable to provide extra time in order to avoid an incorrect overrun correction or false
leakage alarms.
Note that the next batch can only be started after elapsing of this overrun time!
The minimum overrun time is 0.1 second, maximum 999.9 seconds
0.1 - 999.9 seconds
S
ETUP
M
ENU
3 — D
ISPLAY
Below setup options define the display functions for the operator.
SETUP
31
Display
The large 17mm digits can be set to display the actual batched quantity (increase) OR to display
the remaining quantity to be batched (decrease).
increase - decrease
SETUP
32
Backlight
Backlight determines the active color of the optionally supplied LED backlight. If no backlight has
been supplied this setting has no impact.
off - amber - green
SETUP
33
Brightness
Brightness determines the intensity of the optionally supplied LED backlight. If no backlight has
been supplied this setting has no impact.
The following can be selected (from dark to bright):
1 - 2 - 3 - 4 - 5