FT-10 Fill Technical Manual, Rev. 2.21, July 2020
Page 113 of 131
17.2 CC-Link Configuration
FT-10 FILL has one occupied station area on CC-Link network and station type of FT-10 FILL must be
programmed as ‘Remote device station’ in the PLC software. CC-Link configuration for PLC programmers is
shown in
Figure 17.1
– Station information
Input/Output
Definition
Description
Remote Register (RWr)
RWr0, RWr1
1
st
Dword Input (FT-10 FILL Output to PLC Input)
RWr2, RWr3
2
nd
Dword Input (FT-10 FILL Output to PLC Input)
Remote Input (RX)
RX0 ~ RX31
Not used
Remote Register (RWw)
RWw0, RWw1
1
st
Dword Output (PLC Output to FT-10 FILL Input)
RWw2, RWw3
2
nd
Dword Output (PLC Output to FT-10 FILL Input)
Remote Output (RY)
RY0 ~ RY31
Not used
17.3 CC-Link Data Structure
For Data Structure for CC-Link see Appendix,
page 116